National-instruments Quadrature Input Module FP-QUAD-510 Uživatelský manuál Strana 11

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 12
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 10
© National Instruments Corp. 11 FP-QUAD-510
Specifications
The following specifications are typical for a range of
–40 to +70 °C, unless otherwise noted.
Encoder Input
Number of channels..........................4
Input type
Single-ended...............................V
IL
= 0.0–0.8 V
V
IH
= 2.0–250.0 V
Differential .................................±0.3 V provided one input
falls between 0.0 and 3.0 V
and the other input falls
between 0.0 and 250 V
Maximum protected input voltage....±250 VDC on each input
Input bandwidth................................250 kHz for each input
Encoder frequency............................1 million counts/second
Minimum input pulse width..............2 µs
Isolation ............................................2,500 Vrms
Safety isolation, working voltage .....250 Vrms, designed per
IEC 1010 as double insulated
External supply voltage (V)..............8 to 30 VDC, user-provided
at 5 W
I/O supply voltage (Vsup) ................5 VDC at 600 mA maximum
Physical
Indicators ..........................................Green POWER and READY
indicators
Weight...............................................143 g (5.1 oz.)
Power Requirements
Power from network module ............1.2 W maximum
Environment
Operating temperature ......................–40 to +70 °C
Storage temperature..........................–55 to +85 °C
Relative humidity..............................5% to 90%, non-condensing